Key differences at a glance:
| Comparison Dimensions | iC65 | iC60 |
| Implementation Standards | Compliant with GB and IEC standards | Compliant with EN (European Standard), IEC standards and relevant Australian certifications |
| Divide ability | Commonly available models offer 6kA/10kA, while the iC65N can reach 10kA (1P/2P), offering powerful performance. |
Commonly available models have a breaking capacity of 6kA / 10kA / 20kA, while some models (such as the iC60N) can break up to 20kA at 220V. |
| Product Series | iC65 sub-series under the Acti9 series | iC60 sub-series under the Acti9 series |
Detailed technical specifications:
1. General technical parameters
The following parameters are basically the same for the iC65 and iC60 series:
| Parameters | Specifications |
| Rated current (In) | 1A ~ 63A |
| Extreme number | 1P, 2P, 3P, 4P |
| Rated voltage (Ue) | 230V (1P) / 400V (2P/3P/4P) |
| Rated insulation voltage (Ui) | 500V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Operating frequency | 50/60 Hz |
| Mechanical life | 20,000 times |
| Electrical life | 10,000 times |
| Operating ambient temperature | -35℃ ~ +70℃ |
| Storage temperature | -40℃ ~ +85℃ |
| Protection level | IP20 (body) / IP40 (indoor mounting) |
| Pollution level | Level 3 |
| Overvoltage category | IV |
| Traffic limiting level | Level 3 |

Size and Function:
Both the iC65 and iC60 belong to the Schneider Acti 9 series, and their modular mounting dimensions and electrical accessories are interchangeable, allowing for seamless use.
📏 Physical Dimensions: Completely Identical
Both use a standard 18mm width module (1P is 18mm, 2P is 36mm, and so on), supporting 35mm DIN standard rail mounting.
● Width: 18mm per pole (1 module). For example:
○ 1P circuit breaker width = 18mm
○ 2P circuit breaker width = 36mm
○ 4P circuit breaker width = 72mm
● Height: Approximately 84mm - 91mm (slight variations depending on accessories)
● Depth: Approximately 73.5mm - 77mm
▏ When planning installation within a distribution box, space can be calculated based on the uniform dimensions.
🔧 Universality and Accessories: Fully Compatible
This is the core of their interchangeability—all electrical accessories for the iC65 and iC60 are interchangeable.
1. Standard Accessories are Universal:
○ Official Confirmation: Schneider Electric officially states that the iC60N DT two-terminal circuit breaker can be fitted with iC65 electrical accessories (such as iMN, iMX, iOF, etc.).
○ Accessory List: Shunt trip units (iMX), auxiliary contacts (iOF), alarm contacts (SD), overvoltage and undervoltage accessories, etc., are all universally compatible.
2. Residual Current Device (RCD) Accessories are Universal:
○ Vigi iC65 RCD accessories are clearly marked as compatible with both the iC60 and iC65 series circuit breakers.
3. Wiring Accessories are Universal:
○ Comb busbars compatible with iC65 are also compatible with iC60 and can be used with confidence.

Applicable Scenarios and Core Value
"One device, global access"
Product Recommendation: iC65
![]() |
● Applicable Scenarios: |
|
○ Automobile manufacturing, rail transportation, food and pharmaceutical, environmental monitoring, shipbuilding, oil and power, machinery and textile industries ○ Machinery and equipment manufacturing, control system panel manufacturing ○ Power transmission and distribution panel manufacturers, public utilities, building construction, airports |
|
| ● Core Values: | |
|
○ Complete certifications (CE/CB/CCC), equipment is exported globally ○ DC series covers 1500V, meeting the needs of new energy sources ○ Resistant to moisture, salt spray, and vibration, adaptable to harsh environments |
"One series, covering all installation standards"
Product Recommendation: iC60
![]() |
● Applicable Scenarios: |
|
○ Power distribution protection in industrial and commercial buildings ○ Industrial environments with high inductive loads and switching surges ○ Power distribution networks in harsh environments such as dust and humidity |
|
| ● Core Values: | |
|
○ Complies with both IEC/EN 60898-1 (residential/similar applications) and IEC/EN 60947-2 (industrial applications) standards ○ The iC60H model is particularly suitable for polluted network environments, offering strong electromagnetic interference immunity ○ Resists grid interference, ensuring service continuity, and suitable for sensitive electronic equipment circuits |